Drawout MCC Plugin Type

logo-ul-verified

Features at a glance

  • Type tested to conform to leading Global Product Standards. (IEC-61439-1 & 2).
  • Fully Compartmentalized (Form IV) Design.
  • Drawout modules are simply pushed in for withdrawal, ensuring smooth & tool-less operation.
  • Drawout modules plug-in directly on to Vertical Bus Bar, minimizing maintenance issues.
  • Vertical Bus is Joint-free along the feeder area, therefore is highly reliable.
  • Safety shroud/shutter providing IP 20 levels of segregation upon withdrawal.
  • Shock-free operation with Double Stab-in earthing in all Drawout modules.
  • Fully Bolted Modular Structural design.
  • Drawout Modules have interlocks for Test, Service & Isolated positions.
  • Drawout Modules available in 3 Pole for Starter feeders & 4 Pole for Power feeders.
motrcon-2200-nxg-p-2
motrcon-2200-nxg-p-graph
motrcon-2200-nxg-p-2
  • Drawout Modules available in sizes of 150mm & 200mm to 900mm in multiples of 100mm in height.
  • Feeder width increased to 600mm & depth increased to 350mm to ensure compactness.
  • Upto 11 feeders in one vertical stack.
  • Max. possible feeder rating upto 150kw DOL possible in 900mm.
  • Drawout Power & Control Contacts tested as part of Drawout Module during Full Type Test for Temperature Rise, Milli-volt Drop & other related tests in accordance with IEC-61439-1 & 2.
  • Drawout Power Contact ratings:
    • 63A | 250A | 400A
    • Available in 1 Pole, 2 Pole, 3 Pole & 4 Pole.
motrcon-2200-nxg-p-3
motrcon-2200-nxg-p-4
  • Feeder width of 600mm with 24/42 pin control terminals.
  • Minimum feeder size of 150mm can accommodate 42 control terminals.
  • Keeping the modules very compact and making the panel space efficient.
  • Drawout Control Contact ratings:
    • 12A.
    • Available in 24-Way & 42-Way Blocks.

Specifications

STANDARDS IS 8623, IEC 61439 – 1&2
Insulation Characteristics Clearance > 20 mm
Creepage distances > 20 mm
Overvoltage category II / III / IV
Pollution degree 3
Field condition Inhomogeneous (Non-uniform)
Electrical Characteristics Voltage ratings Rated operational voltage (U ) e 415-690 VAC, 24-220 VDC
Rated insulation voltage (U ) i 690 V
Rated impulse withstand voltage (U ) imp 6 / 8 kV
Rated frquency (f ) n 50 / 60 Hz
Current Ratings Main Horizontal busbars:
Rated current (I ) nA up to 4000 A
Rated peak withstand current (I ) pk up to 105 kA
Rated short-time withstand current (I ) cw up to 50 kA, 1s
Vertical Distribution busbars :
Rated current (I ) nA 960A
Rated peak withstand current (I ) pk up to 105 kA
Rated short-time withstand current (I ) cw up to 50 kA, 1s
Mechanical Characteristics Degree of protection In accordance with IEC 60529:
External IP 4X/54
Internal IP 2X
Forms of separation as per IEC 61439 – 2 Form III/IV
Dimensions Height (mm) 2200, 2400
Width (mm) 600, 700, 800, 900, 1000, 1100 (ACB section)
1000, 1300, 2200 (Outgoing section)
Depth (mm) 800, 1000, 1200 (ACB section)
800, 1000, 1200 (Outgoing section)
Surface Treatment Structure GI-280 / powder coated / painted
Internal Components GI-280 / powder coated / painted
External Components Powder coated / painted
Resistance to Connection Damp heat cycling test EC 60068-2-30
Salt mist test IEC 60068-2-11
Plastic Components Flame retardant, self-extinguishing, Halogen-free IEC 60695-2-10, IEC 60695-2-11

Partnering you... Step up to World Standards.